Built with efficiency and hotter climates in mind, the BITMAIN ANTSPACE HK3 (known as model designation Antbox H3 V2 internally) has a maximum capacity of 210 units Rack Space.
![](https://cdn.shopify.com/s/files/1/0620/5168/0446/files/f.png?v=1658248468)
Bitmain’s First Liquid Cooling Antbox
![](https://cdn.shopify.com/s/files/1/0726/4819/6399/files/Screenshot-2022-01-25-at-12.37.16-AM.png?v=1679897468)
Diagram of Liquid Cooling Antbox water circuit
![](https://cdn.shopify.com/s/files/1/0726/4819/6399/files/Screenshot-2022-01-25-at-12.39.21-AM.png?v=1679897494)
Specifications
Input voltage, V | 415±5% AC/60Hz/3P/N/PE |
---|---|
Total power consumption, kW (load shared by two power distribution cabinets) |
1047 |
Miner power consumption W | 4900-5400 |
Miner inlet/outlet water temperature, ℃ | 35/45 |
Container size (length * width * height) | 6058*2438*2896 |
Cooling tower size (length*width*height) | 5800*2240*4286 |
Weight, T (empty weight of cooling tower/operating weight) | 6/10 |
Weight, T (container without miner/with miner weight) | 8/12 |
Cooling tower spray flow, m³/h | 233 |
Heat dissipation capability kW | 1000 |
Inlet and outlet temperature rise ΔT,° | 10 |
Cooling tower docking interface specifications | DN125 |
Heating docking interface specifications | DN100 |
Cooling tower water inlet specifications | DN40 |
Cooling tower drain specifications | DN65 |
Heating piping pressure bearing capability kg | 10 |
Design flow on heating side, m³/h | 85 |
Temperature variation between inlet and outlet(heating side)ΔT | 10 |
Environmental Requirementss
1 | Cooling tower is required to be placed on flat ground, horizontal degree (±1 degree). |
2 | The ground surfaced is required to be hardened and stable, able to withstand at least 14-ton load. |
3 | A 10-ton crane is needed for unloading ANTSPACE and cooling tower. |
4 | Add-on items such as stairs, transformers, cables, bridge racks and cable distribution boxes are not included in the delivery of ANTSPACE. We team can provide design suggestions if needed. |
5 | Client needs to confirm the opening directon of container and it needs to face air-intake. Door on left is current design by defult. |
6 | Keep at least 2 meters of air in-take space around the cooling tower. |
7 | Altitude: ≤3000m. If the altitude is higher than 1000-meter, transformer and switch should be derated, the total power of ANTSPACE must be decreased by 1% for each elevation increment of 100 meters. |
8 | Operating temperature: -25°C to 40°C. Operating humidity: 10%RH to 90%RH. When the initial coolant temperature is below 20 °C, the internal circulation should be turned on to heat up the coolant to above 20 °C before starting the mining machine. |
9 | When the ambient temperature is below 5 ℃, the cooling tower can be switched to cold-dry mode. |
10 | Choose pure water or suitable antifreeze as coolant based on local climate conditions. |
11 | The suitable ambient temperature for ANTSPACE does not represent the suitable ambient temperature for mining machine. |